ABB Bailey INICT13A INFI-NET to PC Interface | PCMCIA/ISA Emulation, CRC-16, 2 ms Latency

ABB Bailey INICT13A INFI-NET to PC Interface | PCMCIA/ISA Emulation, CRC-16, 2 ms Latency

 

Description

The INICT13A​ is an ABB Bailey INFI-NET Computer Transfer module — the rack-side interface that lets a host computer, OIS workstation, or historian talk directly to an INFI 90 / Harmony control network. It is not a controller and it is not a communication module in the plant-I/O sense; it is the dedicated bridge between the INFI-NET coax backbone and the serial or bus-master path that a PC or server expects.

What makes the INICT13A​ worth its weight in a 1990s DCS rack is the job it quietly does: it hands the host a memory-mapped, polled window onto the INFI 90 data space without the host ever having to understand INFI-NET timing, token passing, or the C-net/INFI-NET protocol stack. For a plant still running a Bailey rack because the process is proven, that is the difference between a live historian feed and a manual clipboard.

 

Application Scenarios

Picture a combined-cycle plant where the Bailey INFI 90 rack has been the turbine and boiler interface since the mid-nineties. The OIS still works, but the site wants a modern historian, a web dashboard, and a maintenance-analytics feed without rewriting a single control loop or touching the INFI-NET token. The rack already carries an INICT13A​ in the transfer slot, talking to an old OIS box over RS-232.

When that OIS host finally dies — bad PCMCIA card, dead ISA backplane, no replacement parts — the reflex is to declare a DCS migration. It is the expensive answer. The cheaper one is to keep the INICT13A​ exactly where it is, re-point the serial side at a small industrial PC or a protocol gateway, and keep the INFI-NET traffic untouched. The control loops never know the host changed, the historian gets its feed, and the migration gets pushed to a scheduled shutdown instead of an emergency Saturday. That is the product’s real value: it is the last thing anyone wants to fail, because it is the only door between a living DCS and the rest of the century.

 

Parameter

Main Parameters Value/Description
Product Model INICT13A​ — ABB Bailey INFI-NET Computer Transfer module, INFI-NET 1 interface
Manufacturer ABB Process Automation, originally Bailey Controls / Elsag Bailey
Product Category DCS Communication / Computer Transfer Module (INFI 90 / Harmony INFI-NET interface)
Network Interface INFI-NET 1, 10 Mbps Manchester-encoded coax; BNC 50 Ω, transformer-isolated
Transfer Medium RG-58 / RG-213 coaxial trunk; M5147-CA​ (15 m) or M5147-CB​ (30 m) drop cables
Segment Length 500 m per coax segment; standard INFI-NET topology and terminator rules apply
Host Interface Dual-port RAM / bus-master style transfer; presents a memory-mapped window to the host adapter
Serial Paths 2× RS-232/422/485 ports, independently jumperable; 1× console port at 9600 bps
Serial Baud 300…19 200 bps, software-selectable; 19.2 kbps is the practical ceiling for polled transfer
Buffer / RAM 8 KB dual-port SRAM on the module — the actual hand-off zone between INFI-NET and host
Transfer Mode Host polls module registers; module maintains the INFI-NET side autonomously (store-and-forward)
Error Control CRC-16 on the INFI-NET frame; module retries the INFI-NET side before the host ever sees a NAK
Latency ≈2 ms module-side hand-off; end-to-end is dominated by serial baud and host poll interval
Diagnostics TX/RX frame counts, CRC error count, collision/retry count, link-status LED, module self-test on insertion
Backplane INFI 90 module bus, single-slot transfer position in the local rack (IM/ICIM carrier)
Environmental 0…60 °C operating, 5…95% RH non-condensing; designed for rack-mount cabinet use
Mechanical Single-width INFI 90 module, ≈265 g, edge-connector seating, no external power wiring
Configuration Module + transfer-table build in the INFI 90 engineering station; host driver maps the DP-RAM window
Status Discontinued / legacy platform — supplied as tested surplus, refurbished, or exchange stock