Allen-Bradley 1734-ACNR POINT I/O Adapter – End of Life, Replacement 1734-AENTR

Allen-Bradley 1734-ACNR POINT I/O Adapter – End of Life, Replacement 1734-AENTR

The Allen-Bradley 1734-ACNR is a POINT I/O ControlNet network adapter that serves as the communication interface between ControlNet controllers and POINT I/O modules mounted on the POINTBus backplane. As a member of the Rockwell Automation POINT I/O family, the 1734-ACNR enables high-speed, deterministic data transfer for time-critical applications, managing data exchanges between controllers on the ControlNet network and up to 64 POINT I/O modules . The adapter contains a built-in power supply that converts 24V DC field power to 5V DC backplane power for the POINT I/O modules, supporting the entire line of POINT I/O modules including digital, analog, and specialty I/O types .

Rockwell Automation has announced that the 1734-ACNR will be discontinued as of March 31, 2027. Customers are encouraged to migrate to the 1734-AENTR EtherNet/IP adapter as the engineering replacement . Despite this end-of-life status, the 1734-ACNR remains widely deployed in existing ControlNet installations and continues to be supported through documentation, firmware updates, and available inventory.

The 1734-ACNR supports redundant media configurations, providing network resilience through dual ControlNet cable connections . A Network Access Port (NAP) on the front panel offers local bidirectional access for programming, maintenance, and I/O monitoring without disrupting the primary network connection . The adapter features diagnostic indicators for network and I/O status, enabling rapid troubleshooting of communication faults and module health . Compatible with ControlLogix, FlexLogix, and SoftLogix (5800) controllers, the Series A version of the 1734-ACNR is not compatible with PLC-5 or SLC processors .

Allen-Bradley 1734-ACNR POINT I/O Adapter – End of Life, Replacement 1734-AENTR

 

Technical Specifications

Parameter Name Parameter Value
Product Model 1734-ACNR
Manufacturer Allen-Bradley (Rockwell Automation)
Product Type POINT I/O ControlNet Network Adapter
Input Voltage (Nominal) 24V DC
Input Voltage Range 10…28.8V DC
Field Side Power Requirements 425 mA @ 24V DC (28.8V DC max)
Inrush Current 6 A for 10 ms
POINTBus Current 1000 mA @ 5V DC ±5% (4.75…5.25V)
Power Consumption at 24V 8.0 W
Power Dissipation (Max) 2.8 W @ 28.8V
Input Overvoltage Protection Reverse polarity protected
Maximum POINT I/O Modules 64 modules
Maximum Rack Connections 5 (digital modules only)
Maximum Direct Connections 25 (required for analog/specialty modules)
Scheduled Transmit Data Memory 586 bytes
Operating Temperature -20…55 °C (-4…131 °F)
Country of Origin Singapore
Standard Warranty 1 year
Lifecycle Status End of Life (Discontinued March 31, 2027)
Replacement Product 1734-AENTR

 

Main Features and Advantages

ControlNet Network Integration with Redundant Media: The 1734-ACNR connects POINT I/O systems to ControlNet networks with support for redundant media configurations, providing network resilience through dual cable paths . This redundancy ensures that a single cable fault does not interrupt I/O communication, maintaining process availability in critical applications. The adapter manages data transfers between ControlNet controllers and POINTBus backplane modules, enabling deterministic, high-speed exchange of time-critical I/O data .

Flexible Connection Architecture with Multi-Controller Support: The 1734-ACNR supports up to 5 rack I/O connections and 25 direct I/O connections, allowing multiple controllers to establish communication with POINT I/O modules through a single adapter . Digital modules using Rack Optimization communication format can share rack connections, while analog and specialty modules require direct connections. This architecture enables distributed control strategies where different controllers can own different I/O modules within the same POINT I/O station .

Integrated Power Supply with Backplane Current Capacity: The 1734-ACNR contains a built-in power supply that converts 24V DC field power to 5V DC backplane power, delivering up to 1.0A of backplane current for POINT I/O modules . When additional backplane current is required, the 1734-EP24DC Backplane Extension Power Supply can add up to 1.3A, enabling the maximum configuration of 63 modules (with no more than 25 analog or specialty modules) .

Removal and Insertion Under Power (RIUP): The 1734-ACNR supports RIUP, allowing POINT I/O modules to be removed and inserted while backplane power remains active . This capability significantly reduces mean time to repair by enabling module replacement without system shutdown. Combined with removable wiring systems that keep terminal bases in place, RIUP minimizes downtime during maintenance and troubleshooting .

Comprehensive Diagnostics and Network Access Port: The 1734-ACNR features LED diagnostic indicators for module status, network status (A/B channels), and POINTBus status, providing clear visual feedback for normal operation and fault conditions . A Network Access Port (NAP) on the front panel enables local connection of programming terminals for configuration, monitoring, and troubleshooting without disturbing the ControlNet network .