Technical Specifications
| Parameter | Value |
|---|---|
| Product Model | 70BT01C (Order Code: HESG447024R1) |
| Additional Part Numbers | HEB67077-31B, HE664174-318/21, HE664174-318/23 |
| Manufacturer | ABB (Origin: Sweden/Switzerland) |
| Product Type | Bus Transmitter Module / Isolation Amplifier |
| Compatible System | ABB PROCONTROL P13 / P14 DCS |
| Primary Function | Interface between PROCONTROL-PS protection system and main P-Bus |
| Communication Protocol | ABB PROCONTROL proprietary bus / P-Bus |
| Data Rate | Up to 500 kbps |
| Input Signals | Up to 32 binary or analog inputs |
| Output Signals | 32 PROCONTROL P-Bus signals |
| Galvanic Isolation | 1500 V DC (channel-to-system) |
| Power Supply | 24 V DC (backplane-powered) |
| Supply Voltage Range | 10.5–45 V DC (no load); IS version ≤ 30 V DC |
| Ripple Tolerance | Per HART FSK “Physical Layer” spec Rev. 8.1 |
| Power Consumption | < 10 W (typical 3–5 W) |
| Configuration | Via PDDS; non-volatile EEPROM storage |
| Redundancy | Compatible with redundant communication architectures |
| Operating Temperature | -20 °C to +60 °C |
| Storage Temperature | -40 °C to +85 °C |
| Relative Humidity | 0–95% RH, non-condensing |
| Protection Rating | IP20 (control cabinet installation) |
| Mounting Method | PROCONTROL P13 system rack insertion |
| Diagnostics | Communication status monitoring, fault detection, error reporting |
| Dimensions (H×W×D) | Approx. 16 × 202 × 147 mm |
| Weight | Approx. 0.25 kg |
| Certifications | CE, UL, CSA; compliant with IEC 61131 |
| Environmental | Vibration per IEC 60068-2-6; Shock per IEC 60068-2-27 |
| Protection Features | Reverse polarity protection; IS version voltage-limited for hazardous areas |
| Warranty | 12 months |
Main Features and Advantages
The 70BT01C HESG447024R1 derives its exceptional reputation in the power and process industries from a combination of signal-integrity engineering, robust isolation, and seamless system integration. At its core, the 70BT01C HESG447024R1 solves the most critical challenge in protection-system architecture: how to safely and reliably transport trip commands, status signals, and measurement data from the PROCONTROL-PS protection layer into the main PROCONTROL P control bus without compromising electrical independence or signal fidelity.
Galvanic isolation for absolute safety:
The 1500 V DC galvanic isolation built into the 70BT01C HESG447024R1 creates a hard electrical barrier between the protection system and the control bus. This isolation mitigates ground-loop interference, prevents fault currents from propagating across system boundaries, and protects sensitive control electronics from transients originating on the protection side. In power generation applications—particularly turbine control and generator protection—this isolation is not a luxury but a fundamental safety requirement.
High-density signal integration:
With support for up to 32 binary or analog input channels converted into 32 synchronized P-Bus output signals, the 70BT01C HESG447024R1 consolidates an entire protection signal marshalling zone into a single module. This high channel density dramatically reduces rack space, wiring complexity, and total installed cost while maintaining deterministic, real-time signal availability across the remote bus. The 500 kbps data rate ensures that even the most time-critical trip commands reach the controller within milliseconds.