Product Overview

The 95DSS2E-1​ is Fireye’s enhanced Model InSight flame scanner, representing the pinnacle of the InSight 95 series of microprocessor-based flame detection devices for industrial combustion safety. As a fully integrated dual-spectrum scanner, the 95DSS2E-1​ combines ultraviolet (UV) and infrared (IR) solid-state sensors within a single ruggedized housing, eliminating the need for a separate remote flame amplifier and dramatically simplifying burner management system (BMS) architecture. This self-contained design places the flame relay, fault relay, 4-20mA analog output, electronic self-check circuitry, 8-character alphanumeric LED display, and 4-button keypad all inside the scanner body, making the 95DSS2E-1​ a true “smart” flame sentinel for the most demanding combustion applications.

The core technological advantage of the 95DSS2E-1​ lies in its dual-detector philosophy: the UV sensor responds in milliseconds to the characteristic ultraviolet radiation emitted at flame ignition, while the IR channel continuously analyzes flame flicker frequency to discriminate between true combustion and false signals from hot furnace walls, glowing refractory, or background thermal radiation. This UV+IR fusion detection mode provides unmatched immunity to false alarms, a critical capability for multi-fuel boilers, ethylene cracker furnaces, and sulfur recovery units where conventional single-spectrum detectors struggle. The 95DSS2E-1​ operates on a standard 24 VDC supply and communicates flame status through a built-in SPST-NO flame relay and series-connected SPST-NC fault relay, while simultaneously delivering a proportional 4-20mA signal for remote flame intensity monitoring in the control room.

Engineered for harsh industrial environments, the 95DSS2E-1​ features a cast aluminum housing with grey polyester powder coating, rated NEMA 4X / IP66 for dust-tight, watertight operation in high-temperature, high-vibration, and high-EMI combustion enclosures. The scanner’s electronic self-check system requires no mechanical shutter, eliminating a traditional wear point and significantly extending operational life. With 21 selectable flame flicker frequencies (23-179 Hz), 4 programmable configuration profiles (A/B/C/D), and AutoTune automatic programming, the 95DSS2E-1​ adapts intelligently to virtually any fuel type—gas, oil, coal, or mixed-fuel combustion—while meeting FM, CSA, CE, and UL safety certification standards. For plant engineers responsible for burner safety in power generation, refining, petrochemical, cement, and waste-to-energy applications, the 95DSS2E-1​ delivers the reliability, intelligence, and maintenance simplicity required to keep critical combustion systems running safely and efficiently.

 

Technical Specifications

Parameter Value
Product Model 95DSS2E-1
Manufacturer Fireye (Honeywell Combustion & Fire Safety)
Product Type Enhanced Model InSight Flame Scanner
Series InSight 95 Series
Detection Principle Dual solid-state sensors: UV (295-320 nm) + IR (700-1700 nm)
Detection Modes UV only, IR only, UV+IR fusion
Power Supply 24 VDC (+10% / -15%)
Typical Current 0.35 A
Power Consumption 8.5 VA
Flame Relay SPST-NO, built-in, adjustable ON/OFF threshold
Fault Relay SPST-NC, connected in series with flame relay
Analog Output 4-20 mA, maximum load 750 Ω
Flame Failure Response Time (FFRT) 1-6 s (default 1 s, configurable per safety regs)
Ignition Delay (OTD) 1-6 s, configurable
Flicker Frequencies 21 selectable (23-179 Hz)
Programmable Profiles 4 sets (A/B/C/D)
Self-Check Electronic self-test, no mechanical shutter
Display 8-character alphanumeric LED
User Interface 4-button keypad for setup and diagnostics
Ambient Operating Temperature -40°C to +65°C
Internal Temperature -40°C to +81°C
Humidity 0%-95% non-condensing
Purge Air Requirement Clean dry air, 4 SCFM (113 L/min) minimum; 15 SCFM (425 L/min) for high-temp/dusty environments
Housing Cast aluminum, grey polyester powder coated
Protection Rating NEMA 4X / IP66
Hazardous Area Certification Class I Div. 2 (A/B/C/D), Class II Div. 2 (F/G)
Safety Certifications CE, UL/CSA, FM, RoHS Compliant
Electrical Connection 12-pin quick disconnect or 10 ft (3 m) captive cable
Relay Rating Min: 10 mA 5 VDC; Max: 2 A 30 VDC / 2 A 240 VAC
Detection Distance Up to 30 m (depending on flame size and fuel type)
Weight Ambient model approx. 1.96 kg; CG model approx. 2.89 kg
Communication Fireye dedicated software for remote configuration & monitoring (S2 enhanced features)
Lifecycle Status Active, in production, continuously supplied by OEM
Scroll to Top