The GE IS220PDIAH1A is a Discrete Input Pack designed for use with GE’s Mark VIe series control systems, primarily for turbine control applications. It serves as an interface module to receive digital signals from field devices such as switches, limit switches, and other discrete sensors. The module converts these field signals into a format that can be processed by the Mark VIe control system for monitoring and control logic. It typically features optical isolation on all input channels to enhance system reliability and protect against electrical noise and transients.  

Product Parameters & Specifications (Based on available information):

  • Compatibility: GE Mark VIe series control systems  
  • Number of Channels: 24 discrete input channels  
  • Input Voltage: Typically 28 VDC (verify with the specific datasheet as other voltage options might exist depending on the terminal board used)
  • Input Current: 0.23 A max (when used with specific terminal boards like IS200STCIH1A, IS200STCIH2A, IS200STCIH8A, IS200TBCIH2C, IS200TBCIH4C)
  • Input Isolation: Optical isolation up to 1500 V on all inputs  
  • Scan Rate: (Information not readily available, consult the Mark VIe system specifications)
  • Power Supply: Supplied by the backplane of the Mark VIe control system
  • Operating Temperature: -40 to +70°C (-40 to +158°F)  
  • Mounting: Directly connects to a Discrete Contact Input Terminal Board (e.g., IS200STCIH1A) within the Mark VIe I/O rack.
  • Size: 15.9 cm (high) x 17.8 cm (width) (approximate dimensions of the pack itself, terminal board dimensions will vary)  
  • Hazardous Location Certifications: ATEX Zone 2, Group IIC (when used with specific terminal boards and configurations – verify specific certifications on the datasheet)  

Scroll to Top