Technical Specifications
| Parameter Name | Parameter Value |
|---|---|
| Product Model | 1746-NT8 |
| Manufacturer | Allen-Bradley (Rockwell Automation) |
| Product Type | Analog Input Module (Thermocouple/mV) |
| Platform | SLC 500 (1746 I/O) |
| Number of Input Channels | 8 (independently configurable) |
| Input Signal Types | Thermocouple J, K, T, E, S, R, B, N; ±100 mV |
| Resolution | 16-bit (plus sign) |
| Conversion Type | Integrating ADC with auto-zero |
| Overall Accuracy | ±0.1% of full scale (typical) |
| Temperature Drift | ±50 ppm/°C (gain), ±2 μV/°C (offset) |
| Input Filter | Programmable (2 Hz, 4 Hz, 8 Hz, 16 Hz) |
| Common Mode Rejection | >120 dB at 60 Hz |
| Normal Mode Rejection | >60 dB at 60 Hz |
| Input Protection | 24V AC/DC continuous, 250V AC/DC transient |
| Backplane Current Draw | 175 mA @ 5V DC |
| Power Dissipation, Max | 2.5 W |
| Cold Junction Compensation | Automatic, built-in sensor |
| Open Thermocouple Detection | Yes, software-selectable direction |
| Operating Temperature | 0°C to 60°C (32°F to 140°F) |
| Storage Temperature | -40°C to 85°C (-40°F to 185°F) |
| Certifications | CE, UL, cULus, CSA, ATEX, IECEx, RoHS |
| Dimensions (W x H x D) | 5.7 x 6.6 x 5.8 in (145 x 168 x 147 mm) |
Main Features and Advantages
The 1746-NT8 delivers exceptional analog measurement performance through a combination of high resolution, flexible input configuration, and built-in signal conditioning that eliminates the need for external instrumentation. At the heart of the module is its 16-bit integrating analog-to-digital converter, which provides the resolution necessary to detect even the smallest changes in thermocouple output or millivolt signal. This level of precision is critical in applications such as heat treatment, plastics processing, and food cooking, where temperature must be controlled to within a fraction of a degree to ensure product quality and consistency.
One of the most valuable features of the 1746-NT8 is its ability to accept eight different input types across its channels simultaneously. A single module can, for example, monitor a type K thermocouple on a furnace wall, a type J thermocouple on an exhaust stack, a type S thermocouple in a high-temperature kiln, and a ±100 mV signal from a pressure transducer—all at the same time and all with independent scaling and filtering. This flexibility dramatically reduces the number of modules required in a system and simplifies inventory management, as one module type can cover virtually any low-level analog input requirement.
The 1746-NT8 also incorporates sophisticated signal conditioning features that are essential for accurate thermocouple measurement. Automatic cold junction compensation (CJC) eliminates the need for manual temperature offset calculations, while built-in linearization algorithms convert raw thermocouple millivolt outputs directly into accurate temperature readings in degrees Celsius or Fahrenheit. The module’s high common mode rejection ratio of over 120 dB at 60 Hz ensures that noise from grounded or long-run thermocouple cables does not corrupt the measurement, and its open thermocouple detection feature alerts the control system immediately if a sensor wire breaks or becomes disconnected.
Configuration and calibration are performed using Rockwell Automation’s RSLogix 500 software, which provides an intuitive interface for setting input type, range, filter frequency, alarm limits, and scaling parameters for each channel. The module supports both voltage and temperature engineering units, and all configuration data is stored in non-volatile memory, meaning that settings are retained even if power is lost. The 1746-NT8 also provides comprehensive diagnostic information including over-range and under-range detection, open circuit indication, and module fault status, allowing control programs to respond intelligently to sensor or wiring problems.
Application Field
The 1746-NT8 is deployed in industrial applications where accurate, reliable temperature measurement is fundamental to process control, product quality, and equipment protection. In the plastics and rubber industries, the module is commonly used to monitor barrel zones, nozzle temperatures, mold temperatures, and extruder melt temperatures on injection molding machines and extrusion lines. Its high resolution and built-in linearization ensure that temperature control loops can maintain the tight tolerances required for consistent part quality, while its open thermocouple detection feature provides immediate notification of sensor failure before product scrap can occur.
In heat treatment and thermal processing applications such as annealing, tempering, brazing, and kiln firing, the 1746-NT8 is used to monitor furnace and oven temperatures across multiple zones. Its support for high-temperature thermocouple types S, R, and B makes it well-suited to applications where temperatures exceed the range of standard type K or J sensors. The module’s ability to accept millivolt inputs also allows it to interface with radiation pyrometers and other non-contact temperature sensors, providing flexibility in applications where physical contact with the process is impractical.
Beyond temperature measurement, the 1746-NT8 is used in any application requiring accurate acquisition of low-level analog signals. Food and beverage processors use the module to monitor cooking temperatures, pasteurization parameters, and refrigeration system performance. Chemical plants rely on it for reactor temperature monitoring and control. HVAC and building automation systems use it for precise temperature sensing in large commercial facilities. The module’s robust input protection, wide operating temperature range, and compatibility with the proven SLC 500 platform make it suitable for deployment in control panels subjected to demanding thermal and electrical conditions. Whether monitoring a single critical temperature or acquiring data from eight independent analog sources, the 1746-NT8 provides the accuracy, flexibility, and dependability that industrial measurement applications demand.