Technical Specifications
| Parameter Name | Parameter Value |
|---|---|
| Product Model | 1734-OE2C (Series C) |
| Manufacturer | Allen-Bradley / Rockwell Automation |
| Product Series | Bulletin 1734 POINT I/O® |
| Product Type | 2-point analog current output module |
| Number of Outputs | 2 (single-ended, non-isolated) |
| Output Signal Ranges | 0–20 mA or 4–20 mA, user configurable per channel; 4–20 mA default |
| Output at Startup / Comms Loss | 0 mA until communication is established |
| Resolution | 13 bits over 0–21 mA (≈2.5 µA/count; typical range 2.3–2.7 µA/count) |
| Absolute Accuracy | 0.1% of full scale at 25°C |
| Accuracy Drift with Temperature | 30 ppm/°C |
| Conversion Type | Digital-to-analog converter (DAC) |
| Conversion Rate | 16 µs |
| Step Response (to 63% of FS) | 24 µs |
| Data Format | Signed integer |
| Calibration | Factory calibrated; no field calibration required |
| Output Load Resistance | 0–750 Ω per channel |
| External DC Supply Voltage | 24V DC nominal; 10–28.8V DC range (includes 5% AC ripple) |
| External Supply Current | ≈70 mA at 24V DC (including both outputs at 20 mA) |
| POINTBus Current | 75 mA maximum at 5V DC |
| Power Dissipation, max | 1.0W at 28.8V DC (Rockwell pub.); 1.23W with 750 Ω load per output |
| Thermal Dissipation | 3.4 BTU/hr max (Rockwell pub.); 4.19 BTU/hr with 750 Ω load |
| Isolation Voltage | 50V continuous, basic insulation type; type-tested at 2200V DC for 60 s |
| Channel-to-Channel Isolation | None (single-ended, non-isolated) |
| Indicators | 1 green/red module-status LED; 1 green/red network-status LED; 2 channel-status LEDs (flash red on open-wire or field-power loss) |
| Keyswitch Position | 4 |
| Compatible Terminal Bases | 1734-TB, 1734-TBS, 1734-TB3, 1734-TB3S, 1734-TOP, 1734-TOPS, 1734-TOP3, 1734-TOP3S |
| Terminal Base Screw Torque | 0.6 N·m (7 lb-in) |
| Removable Terminal Block | Yes (RTB) — module can be replaced without disconnecting field wiring |
| Enclosure Type | Open style, IP20 |
| Dimensions (H × W × D) | 56 × 12 × 75.5 mm (2.206 × 0.472 × 2.97 in.) without terminal base |
| Weight | ≈36 g (1.27 oz) |
| Wire Size | 0.25–2.5 mm² (22–14 AWG) solid or stranded copper, 75°C or greater |
| Mounting | DIN rail (35 mm), horizontal or vertical, no derating |
| Removal and Insertion | RIUP (Removal and Insertion Under Power) supported |
| Operating Temperature | −20 … +55°C (−4 … +131°F) |
| Storage Temperature | −40 … +85°C |
| Relative Humidity | 5–95%, non-condensing |
| Vibration Resistance | 5 g at 10–500 Hz |
| Shock Resistance | 30 g operating |
| ESD Immunity | 6 kV contact, 8 kV air discharge |
| Conducted RF Immunity | 10 Vrms, 1 kHz sine, 80% AM, 80–150 MHz |
| Certifications | CE, cULus, UL, C-Tick, KC, MARINE, IECEx Scheme, China CCC, Registro Italiano Navale |
| Country of Origin | Singapore |
| UPC / GTIN | 10612598205292 / 612598205295 |
| Lifecycle Status | Active |
Main Features and Advantages
13-bit resolution with 2.5 µA per count: The Allen-Bradley 1734-OE2C divides the 0–21 mA output span into 8,192 discrete steps, so a full-scale command changes the output in increments of roughly 2.5 µA. In practical terms this means a control valve receives a smoothly varying demand rather than a stepped one, and a VFD speed reference changes in increments too small to register as a speed jump at the motor. The 0.1% full-scale absolute accuracy at 25°C keeps the entire span within specification without field trim, and the 30 ppm/°C drift coefficient ensures that accuracy is held across the operating-temperature range rather than only on the bench.
Fast conversion and step response for real-time loops: With a 16 µs conversion rate and a 24 µs step response to 63% of full scale, the Allen-Bradley 1734-OE2C is materially faster than the update rates of the loops it typically serves. This headroom matters when a PID loop is retuning after a setpoint change or when a valve must track a ramping profile without lag — the analog output is never the limiting element in the loop. The module’s data exchange across the POINTBus backplane consumes four bytes of output data and returns two bytes of input data carrying fault-status information, so the controller always knows the state of each channel.
0 mA output until communication is established: A particularly valuable safety-oriented behaviour of the Allen-Bradley 1734-OE2C is that both outputs sit at 0 mA until communication with the controller is established. During power-up, after a network fault, or while a module is being replaced, a control valve or VFD therefore receives no demand signal and remains in its de-energized state rather than being driven by a stale value left in the DAC. This is the difference between a controlled startup and one that can surprise an operator.
Open-wire and field-power-loss diagnostics: The channel-status LEDs of the Allen-Bradley 1734-OE2C flash red to indicate an open-wire condition or loss of the 24V DC field supply, giving maintenance staff immediate local visibility without opening the programming software. Because the fault information is also returned to the controller via the backplane, the same condition can drive an alarm, trip a safety interlock or be logged as part of a predictive-maintenance record.
Compact footprint with RIUP and removable terminal block: At 12 mm wide, the Allen-Bradley 1734-OE2C occupies a single slot on the POINT I/O node, allowing dense I/O racks without expanding cabinet footprint. Removal and Insertion Under Power (RIUP) permits a faulty module to be changed without shutting down the backplane, while the removable terminal block (RTB) means the field wiring stays connected to the base during the swap — no re-termination, no risk of mis-wiring, and a substantially shorter mean time to repair. The module can be mounted horizontally or vertically with no derating, and the compatible terminal-base family includes screw-terminal, spring-clamp and three-tier variants to suit the wiring method and density of the installation.