GE MMII-PD-1-2-120 Panel-Mount Motor Protection Relay with LCD Display

GE MMII-PD-1-2-120 Panel-Mount Motor Protection Relay with LCD Display

 

Technical Specifications

表格

Parameter Specification
Product Model MMII-PD-1-2-120
Manufacturer GE Multilin (General Electric)
Product Type Intelligent Motor Management and Protection Relay
Product Series Motor Manager II (MM2 / MMII)
Control / Auxiliary Supply 120 VAC nominal, 80–135 VAC operating, 50/60 Hz
Power Consumption < 15 W typical, ≤ 25 VA rated
Current Inputs 3-phase CT secondary, 1 A / 5 A selectable, true RMS
Voltage Input 120 VAC sampled
Measurement Accuracy Current / voltage ±2%
Display and Indication 40-character LCD, 11 status LEDs
Protection Functions Thermal overload (12 I²t curves), phase unbalance, ground fault, stall, over/undervoltage, undercurrent, thermistor
Overload Trip Accuracy ±200 ms (trip ≤ 10 s); ±2% of trip time (> 10 s)
Communication RS-485, Modbus RTU, 1200–19200 bps
Mounting Panel / door cutout; optional DIN-rail adapter
Operating Temperature 0 °C to +60 °C
Storage Temperature -40 °C to +85 °C
Enclosure Rating IP20 (panel face)
Approximate Dimensions 188 × 112 × 127 mm
Approximate Weight 1.36 kg

 

Main Features and Advantages

Comprehensive protection in one device: The ‌GE MMII-PD-1-2-120‌ covers thermal overload with twelve selectable I²t curves, phase unbalance, phase loss, ground fault, locked or stalled rotor, contactor failure, overvoltage, undervoltage, undercurrent, and hot-winding thermistor input. Overload trip accuracy is specified at ±200 ms for trips under ten seconds and ±2% of trip time beyond that, which is tight enough to coordinate with upstream devices rather than trip blindly.

Thermal modeling that reflects real motor behavior: Instead of a fixed-time curve, the ‌GE MMII-PD-1-2-120‌ uses a thermal replica that tracks winding temperature through starting and running conditions. This matters on high-inertia loads — fans, crushers, conveyors — where a conventional overload relay either trips too early during a long start or too late to prevent damage.

Local visibility without a laptop: The 40-character LCD and eleven LEDs on the ‌GE MMII-PD-1-2-120‌ display running current, voltage, thermal capacity used, and trip cause directly at the bucket door. A maintenance technician can diagnose a trip during a walkdown instead of retrieving a configuration tool, which shortens the path from fault to restart.

Communication for plant integration: An RS-485 port running Modbus RTU at 1200 to 19200 bps lets the ‌GE MMII-PD-1-2-120‌ report metering and status to a PLC, DCS, or SCADA layer. Motor starts, run hours, and trip history become part of the plant record rather than a paper log.

Straightforward physical integration: Panel or door cutout mounting with an optional DIN-rail adapter means the ‌GE MMII-PD-1-2-120‌ fits both new MCC construction and retrofit work in existing cabinets, with no special backplane or rack requirement.