Technical Specifications
表格
| Parameter | Specification |
|---|---|
| Product Model | MMII-PD-1-2-120 |
| Manufacturer | GE Multilin (General Electric) |
| Product Type | Intelligent Motor Management and Protection Relay |
| Product Series | Motor Manager II (MM2 / MMII) |
| Control / Auxiliary Supply | 120 VAC nominal, 80–135 VAC operating, 50/60 Hz |
| Power Consumption | < 15 W typical, ≤ 25 VA rated |
| Current Inputs | 3-phase CT secondary, 1 A / 5 A selectable, true RMS |
| Voltage Input | 120 VAC sampled |
| Measurement Accuracy | Current / voltage ±2% |
| Display and Indication | 40-character LCD, 11 status LEDs |
| Protection Functions | Thermal overload (12 I²t curves), phase unbalance, ground fault, stall, over/undervoltage, undercurrent, thermistor |
| Overload Trip Accuracy | ±200 ms (trip ≤ 10 s); ±2% of trip time (> 10 s) |
| Communication | RS-485, Modbus RTU, 1200–19200 bps |
| Mounting | Panel / door cutout; optional DIN-rail adapter |
| Operating Temperature | 0 °C to +60 °C |
| Storage Temperature | -40 °C to +85 °C |
| Enclosure Rating | IP20 (panel face) |
| Approximate Dimensions | 188 × 112 × 127 mm |
| Approximate Weight | 1.36 kg |
Main Features and Advantages
Comprehensive protection in one device: The GE MMII-PD-1-2-120 covers thermal overload with twelve selectable I²t curves, phase unbalance, phase loss, ground fault, locked or stalled rotor, contactor failure, overvoltage, undervoltage, undercurrent, and hot-winding thermistor input. Overload trip accuracy is specified at ±200 ms for trips under ten seconds and ±2% of trip time beyond that, which is tight enough to coordinate with upstream devices rather than trip blindly.
Thermal modeling that reflects real motor behavior: Instead of a fixed-time curve, the GE MMII-PD-1-2-120 uses a thermal replica that tracks winding temperature through starting and running conditions. This matters on high-inertia loads — fans, crushers, conveyors — where a conventional overload relay either trips too early during a long start or too late to prevent damage.
Local visibility without a laptop: The 40-character LCD and eleven LEDs on the GE MMII-PD-1-2-120 display running current, voltage, thermal capacity used, and trip cause directly at the bucket door. A maintenance technician can diagnose a trip during a walkdown instead of retrieving a configuration tool, which shortens the path from fault to restart.
Communication for plant integration: An RS-485 port running Modbus RTU at 1200 to 19200 bps lets the GE MMII-PD-1-2-120 report metering and status to a PLC, DCS, or SCADA layer. Motor starts, run hours, and trip history become part of the plant record rather than a paper log.
Straightforward physical integration: Panel or door cutout mounting with an optional DIN-rail adapter means the GE MMII-PD-1-2-120 fits both new MCC construction and retrofit work in existing cabinets, with no special backplane or rack requirement.