Product Overview
The GE IS220PHRAH1A is the HART-capable analog input/output pack of the PHRA functional family within the Speedtronic Mark VIe turbine control platform, now supported under GE Vernova. It provides ten analog input channels and two analog output channels, and superimposes HART digital communication on those current loops so that a single pair of field wires carries both the process variable and the transmitter’s own diagnostic data. In practical terms the IS220PHRAH1A is the component that lets a Mark VIe cabinet read smart pressure, temperature and flow transmitters and drive analog valves or I/P converters, while giving the control system visibility of device health that a plain 4–20 mA card cannot offer.
Architecturally the IS220PHRAH1A is a blind-mate pack rather than a terminal module. It carries no field screw terminals of its own: field wiring lands on a separate SHRAH-series terminal board, and the pack plugs onto that board, presenting two RJ45 IONet ports and an infrared service port on its face. This separation is deliberate. The terminal board and its wiring stay undisturbed for the life of the unit, while the electronics pack can be changed in minutes during an outage, which is exactly the service model turbine operators depend on when a card fails at an inconvenient moment.
On the network side, the IS220PHRAH1A connects to the dual-redundant IONet Ethernet fabric of the Mark VIe controller, and the same pack type is used in simplex and in triple-modular-redundant arrangements, where three packs run in parallel and the controller votes on their data. That makes the IS220PHRAH1A equally at home in a simple frame and in a high-availability gas turbine application where a single I/O failure must not cause a trip.
One point deserves emphasis for anyone buying spares. GE’s published product lifecycle notice shows the IS220PHRAH1A as an obsolete catalogue number, with the IS220PHRAH1B as its updated-technology replacement. Both describe the same function, ten voltage/current inputs and two 0–20 mA outputs with HART, but the upgrade is not entirely plug-and-play: the controller software and, in some cases, the terminal board and its wiring may need attention, following the service procedure in GE’s BPPC I/O upgrade guide. Where a like-for-like swap is required to keep a machine running, a correctly sourced remains the lowest-risk route.
Technical Specifications
| Parameter Name | Parameter Value |
|---|---|
| Product Model | |
| Manufacturer | GE / GE Vernova |
| Product Series | Speedtronic Mark VIe |
| Product Type | HART Analog Input/Output Pack (PHRA functional family) |
| Alternate Part Number | 336A5027ADP1 |
| Analog Inputs | 10 channels, 4–20 mA or ±5 V DC (range set by terminal board populate) |
| Analog Outputs | 2 channels, 0–20 mA / 4–20 mA current loop |
| Output Load Capability | Up to 800 Ω on 4–20 mA, subject to terminal board revision |
| Input Resolution | 16-bit A/D conversion |
| Output Resolution | 14-bit D/A conversion |
| Measurement Accuracy | Better than 0.1 % of full scale |
| Scan Rate | Approximately 5 ms per channel with two-pole hardware low-pass filter |
| HART Support | HART digital communication on analog input and output loops |
| Network Interface | Dual RJ45 100 Mbps IONet ports, redundant |
| Service Interface | Infrared port on module face |
| Terminal Board Compatibility | IS200SHRAH1A / IS200SHRAH2A |
| Mounting | Blind-mate plug-in on compatible Mark VIe terminal board |
| Power Requirement | Supplied through the terminal board; allow adequate supply headroom for full channel load |
| Operating Temperature | -30 °C to +65 °C |
| PCB Protection | Conformal coated |
| Hazardous Location Rating | Class I Div 2 and Zone 2 where fitted to a certified assembly |
| Product Status | Legacy / superseded by IS220PHRAH1B |