Technical Specifications
| Parameter Name | Parameter Value |
|---|---|
| Product Model | 1747-L524 |
| Manufacturer | Allen-Bradley (Rockwell Automation) |
| Product Type | SLC 5/02 Central Processor Unit |
| User Memory | 4 KB (4,000 instructions) |
| Maximum Discrete I/O | 4,096 inputs / 4,096 outputs |
| Maximum Analog I/O | 480 channels |
| Local Chassis / Slots | 3 chassis / 30 slots |
| Communication Port | DH-485 (built-in) |
| Programming Software | RSLogix 500 |
| Program Scan Time | Approx. 4.8 ms per 1K instructions |
| Backplane Current (5V DC) | 350 mA |
| Backplane Current (24V DC) | 105 mA |
| Operating Temperature | 0°C to +60°C |
| Storage Temperature | -40°C to +85°C |
| Chassis Slot | Slot 0 |
| Status | Discontinued (EOL) |
Main Features and Advantages
The 1747-L524 provides a balanced combination of memory and I/O capacity for mid-range SLC 500 applications. Its 4 KB user memory supports programs with up to 71 programming instructions, a significant increase over the 52-instruction set of the SLC 5/01 . The processor’s 4.8 ms/K scan time is roughly twice as fast as the SLC 5/01, improving responsiveness in control applications with moderate logic complexity.
The built-in DH-485 communication port on the 1747-L524 supports both receiving and initiating communication, allowing the processor to participate actively in a DH-485 network rather than merely listening. Programming requires a 1747-PIC interface when connecting to the DH-485 channel . The 1747-L524 also supports EEPROM memory modules (1747-M2) for program backup, providing a non-volatile storage option in addition to the battery-backed RAM .
For systems requiring backup redundancy, the 1747-L524 is compatible with the 1747-BSN backup scanner module, enabling high-speed backup communication and switchover of Data Highway Plus, remote I/O links, and RS-232 channels in redundant SLC 500 configurations . The processor is certified for Class I, Division 2 hazardous locations (Groups A, B, C, D) and carries c-UL-us and CE markings, making it suitable for installation in environments where flammable gases may be present under abnormal conditions .
Application Field
The 1747-L524 is deployed in SLC 500 systems that require more I/O capacity and faster scan times than the SLC 5/01 can deliver, without the advanced communication features of the SLC 5/03 and above. In manufacturing operations, the controls production equipment with moderate logic requirements, such as packaging machines, assembly stations, and material handling conveyors where up to 4,096 discrete points are sufficient for the application.
Water and wastewater facilities commonly use the for pump station control, valve sequencing, and process monitoring in treatment plants. The processor’s 480-channel analog capacity supports level, flow, and pressure monitoring alongside discrete control of motors and valves. In building automation and HVAC applications, the manages chiller plants, air handling units, and boiler controls where the DH-485 network connects multiple SLC 500 processors and operator interfaces across a facility.
Because the is discontinued, current applications are primarily maintenance and spares for existing installations. Facilities with operational SLC 500 systems should maintain spare processors or plan migration to the CompactLogix platform, as failure of a processor without a replacement on hand can halt production while a suitable substitute is sourced.