Allen-Bradley 1746-OW16 SLC 500 16-Channel Relay Output Module

Allen-Bradley 1746-OW16 SLC 500 16-Channel Relay Output Module

he 1746-OW16​ is a sixteen-channel relay output module from Allen-Bradley, part of the Rockwell Automation SLC 500 family (Bulletin 1746). It is the workhorse discrete-output module for SLC 500 systems that need to switch real contacts rather than solid-state devices: each of the sixteen outputs is an electrically isolated, single-pole normally-open (Form A) relay contact, capable of handling up to 2 A at 250 V AC. The 1746-OW16​ therefore behaves like sixteen independent dry contacts under program control, and it is this contact-based switching that defines its role in the SLC 500 I/O architecture.

The design intent of the 1746-OW16​ is to give the SLC 500 processor a way to drive loads that are too inductive, too high-voltage, or too electrically hostile for a transistor output, and to do so without requiring interposing relays in the panel. Each output is independently fused and protected against overload, and the module carries backplane current of 780 mA at 5 V DC while drawing 2 mA at 24 V DC. Status indication is handled by a single green module-status LED plus two red LEDs that identify overload and fuse-blown conditions, so a maintenance technician can distinguish a module fault from a field-device or wiring problem without opening the cabinet door or pulling the module.

Rockwell Automation discontinued the 1746-OW16​ as part of the broader SLC 500 end-of-life, effective October 31, 2023, with the replacement classification listed as “Other” — meaning no direct functional replacement was offered by the manufacturer. This is the central fact for anyone supporting an installed SLC 500 system: the 1746-OW16​ cannot simply be swapped for a Compact 5000 or ControlLogix equivalent without a platform and I/O migration. A tested 1746-OW16​ is therefore not merely a spare part but the enabling component that keeps a commissioned, validated SLC 500 system running without a project-level conversion.

Allen-Bradley 1746-OW16 SLC 500 16-Channel Relay Output Module

 

Technical Specifications

Parameter Name Parameter Value
Product Model 1746-OW16
Manufacturer Rockwell Automation / Allen-Bradley
Product Type SLC 500 Relay Output Module
Product Family / Platform Bulletin 1746 SLC 500
Number of Outputs 16, normally open (Form A / SPST-NO)
Output Type Electromechanical relay, dry contact
Isolation Electrically isolated outputs
Contact Rating @ 250 V AC 2 A per point (resistive)
Contact Rating @ 125 V AC 4 A per point (resistive)
Contact Rating @ 24 V DC 2 A per point
Contact Rating @ 48 V DC 1 A per point
Maximum Load Current 2 A per point; 32 A total backplane
Surge Current 10 A for 100 ms
Minimum Load Current 10 mA
Initial Contact Resistance 30 mΩ
Life Expectancy (mechanical) 10,000,000 operations
Life Expectancy (load dependent) 1,000,000 operations at rated load
Maximum AC Switching Voltage 250 V AC
Maximum DC Switching Voltage 125 V DC
Off-State Leakage Current 0 mA
On-State Voltage Drop Less than 1 V
Backplane Current @ 5 V DC 780 mA
Backplane Current @ 24 V DC 2 mA
Power Dissipation 4.5 W (at 60 °C)
Thermal Dissipation 15.4 BTU/hr (at 60 °C)
Field Device Wiring Terminals 20
Fusing Individually fused and overload protected
Status Indicators 1 green module-status LED; 2 red overload/fuse-blown LEDs
Module Location Any slot in SLC 500 chassis (fixed or modular)
Module Width 1 SLC 500 slot
Weight 0.32 kg (0.70 lb)
Operating Temperature 0 to 60 °C (32 to 140 °F)
Storage Temperature -40 to 85 °C (-40 to 185 °F)
Relative Humidity 5 to 95%, non-condensing
Certifications CE, CSA, C-UL, FM, ATEX, IECEx, RCM, CCC
Lifecycle Status Discontinued effective October 31, 2023; “Other” replacement

 

Main Features and Advantages

True dry-contact switching with no leakage:

Because every output on the 1746-OW16​ is an electromechanical relay rather than a transistor or triac, the off-state leakage current is zero. That is a material advantage when the load is a sensitive device, a low-current solenoid, or a circuit where even a few milliamps of leakage would cause a false operation. The contact is a genuine open circuit when de-energized, and the less-than-1 V on-state drop means negligible power loss in the module itself.

One module covers AC and DC switching:

The 1746-OW16​ is not limited to a single voltage class. Its contacts switch up to 250 V AC at 2 A and up to 125 V DC, with a 4 A rating at 125 V AC and 1 A at 48 V DC. A single module type can therefore serve indicator lamps, small solenoids, contactor coils, motor starters, and DC control circuits across the panel. For OEMs and spare-parts programs this universality reduces the number of output-module variants that must be stocked.

Independence and isolation simplify the panel:

The sixteen outputs of the 1746-OW16​ are independently fused and electrically isolated from one another, so a shorted field device or a blown fuse on one point does not disable the other fifteen. This is the kind of fault containment that prevents a single wiring error from taking down an entire machine function, and it removes the need for external interposing relays in many applications.

Diagnostic visibility without a laptop:

The 1746-OW16​ carries three status LEDs — one green for module health and two red for overload and fuse-blown conditions. A technician standing in front of the cabinet can identify a blown fuse or an overloaded point instantly, without opening the programming software or removing the module. In a high-volume production environment this is the difference between a five-minute repair and a protracted fault-finding session.

Allen-Bradley 1746-OW16 SLC 500 16-Channel Relay Output Module1

Scroll to Top