Technical Specifications
| Parameter Name | Parameter Value |
|---|---|
| Product Model | 1746-OBP8 |
| Manufacturer | Allen-Bradley (Rockwell Automation) |
| Product Type | SLC 500 High Current DC Output Module |
| Series | A (Series B and later feature fast turn-off) |
| Output Type | Sourcing (current sourcing) |
| Number of Outputs | 8 points, 2 groups of 4 |
| Operating Voltage | 20.4 to 26.4 VDC |
| Current per Point | 2.0 A at 60°C |
| Current per Module | 8.0 A at 0 to 60°C |
| Backplane Current (5V DC) | 0.135 A |
| Signal Delay (Resistive Load) | On: 1.0 ms / Off: 2.0 ms |
| Surge Current | 4 A per point for 10 ms; 32 A per module for 10 ms |
| Off-State Leakage (Max) | 1 mA |
| On-State Voltage Drop (Max) | 1 V at 2 A |
| Operating Temperature | 0°C to 60°C |
Main Features and Advantages
High Current Capacity Eliminates Interposing Relays: The Allen-Bradley 1746-OBP8 delivers 2.0A per output point and 8.0A per module, a specification that places it well above standard SLC 500 output modules and enables direct control of loads that would otherwise require external relays or contactors. Solenoid valves, motor starters, and actuator coils commonly draw currents in the 1-2A range, and the 1746-OBP8 handles these loads without additional hardware, reducing panel space, wiring complexity, and potential failure points. For applications where panel real estate is limited or where adding interposing relays would require significant rework, the Allen-Bradley 1746-OBP8 provides a compact high-current solution.
Fast Turn-Off Circuitry for Inductive Load Performance: The Allen-Bradley 1746-OBP8 Series B and later revisions incorporate on-board surge suppressors that dramatically reduce OFF delay when switching inductive loads such as contactor coils and solenoids. The module achieves a 47 ms OFF delay when switching a typical sealed 24V contactor, compared to 152 ms for standard SLC output modules . This faster de-energization improves control responsiveness and reduces arcing across relay contacts in downstream circuits. The module’s built-in suppression also means that external diodes or RC snubbers are not required at the load for most inductive applications, simplifying wiring and reducing component count.
Fused Common and Diagnostic Indicators: The Allen-Bradley 1746-OBP8 includes a fused common per output group and a blown fuse LED that illuminates when the fuse opens due to an output short circuit or overload . This diagnostic feature allows maintenance technicians to identify the affected group immediately without performing voltage checks or tracing wiring. The fuse protects the module’s output circuitry from damage due to field wiring faults, and the LED provides a clear visual indication that the module requires service. While the fuse is not user-replaceable in the field on all revisions, the diagnostic indication guides troubleshooting and confirms when module replacement is necessary.
Sourcing Output Configuration for Common-Ground Systems: The provides sourcing (positive-logic) outputs, meaning the module supplies +24V DC to the load when energized, with the load’s return path connected to DC common. This configuration is standard in most Allen-Bradley SLC 500 installations and is compatible with sinking input devices, relay coils with one side grounded, and most industrial control panels wired with a common negative bus. The sourcing design simplifies troubleshooting, as a voltage measurement at the output terminal directly indicates whether the point is energized.