Allen-Bradley 1426-M5E-DNT PowerMonitor 5000 – Basic Meter, EtherNet/IP + DeviceNet, Class 0.2

Allen-Bradley 1426-M5E-DNT PowerMonitor 5000 – Basic Meter, EtherNet/IP + DeviceNet, Class 0.2

 

Product Overview

The 1426-M5E-DNT​ is an Allen-Bradley (Rockwell Automation) PowerMonitor 5000 Basic Module—the M5 base-model unit with native EtherNet/IP communication and a factory-installed DeviceNet option card. It is a revenue-grade power and energy meter whose job is to convert the analog electrical quantities of a three-phase distribution system into digital, network-visible data: volts, amps, watts, vars, VA, power factor, frequency, demand, and bidirectional energy accumulation. The 1426-M5E-DNT​ does not protect equipment or trip breakers; it measures, calculates, logs, alarms, and reports.

Inside the meter, four voltage sense channels (V1, V2, V3, VN) and four current sense channels (I1, I2, I3, I4) are sampled at 1024 points per cycle, per channel—producing 1024 data points across all eight channels every 12 to 17 milliseconds. From that raw stream, the 1426-M5E-DNT​ calculates more than 6,000 parameters every line cycle, including kW, kVA, kVAR, kWh, kVAh, kVARh, demand power factor, displacement power factor, voltage and current unbalance, crest factors for V-V, V-N and I on a per-phase basis, and symmetrical component analysis. The voltage inputs accept up to 690 VAC line-to-line directly (with a line-line metering range of 26–1144 VAC when PT ratio scaling is applied); the current inputs accept 1 A or 5 A secondaries from external current transformers, with a range of 0.05–15.6 A rms.

The value of the 1426-M5E-DNT​ is concentrated in two areas. First, accuracy: it is ANSI C12.20-2010 Class 0.2 and EN 62053-22-2003 Class 0.2, with voltage and current readings accurate to ±0.1% at 25 °C, 50/60 Hz, unity power factor. This makes it suitable for utility-grade sub-metering and tenant or department cost allocation, not merely for casual load monitoring. Second, connectivity: the native EtherNet/IP port carries the CIP Energy object for direct integration with ControlLogix, CompactLogix, FactoryTalk View, and energy management platforms, while the DeviceNet port provides compatibility with legacy DeviceNet scanner systems or simpler SCADA polling. A built-in web server allows local configuration, trend viewing, and I/O status without proprietary software. Add the four digital inputs for WAGES data collection, four outputs for SCADA or control interfacing, and configurable alarms for up to 20 events, and the 1426-M5E-DNT​ is a complete energy node rather than a meter with a network port bolted on.

 

Technical Specifications

Parameter Name Parameter Value
Product Model 1426-M5E-DNT
Manufacturer Allen-Bradley (Rockwell Automation)
Product Type PowerMonitor 5000 Basic Power & Energy Monitoring Module
Product Family Bulletin 1426 PowerMonitor 5000
Model Tier M5 (Basic)
Voltage Sense Inputs V1, V2, V3, VN; ±0.1% accuracy
Voltage Rating (L-N) 398 VAC nominal; 15…660 VAC range
Voltage Rating (L-L) 690 VAC nominal; 26…1144 VAC range (via PT ratio)
Voltage Input Impedance 5 MΩ minimum
Current Sense Inputs I1, I2, I3, I4; 1 A or 5 A secondary from external CTs
Current Range 0.05…15.6 A rms; ±0.1% accuracy
Frequency Range 40…75 Hz (50/60 Hz nominal); ±0.05 Hz accuracy
Measurement Update Rate One update per line cycle; 1024 samples/cycle/channel
Calculated Parameters 6,000+ per cycle
Energy Accuracy ANSI C12.20-2010 Class 0.2; EN 62053-22-2003 Class 0.2
EtherNet/IP Port 10/100 Mbps, RJ45, native, with CIP Energy object
DeviceNet Port 125 / 250 / 500 kbps, option card (factory-installed), consumes <50 mA from 24 VDC bus
Digital Inputs 4 (dry contact / 24 VDC sourced) for WAGES data collection
Digital Outputs 4: 3 form-C relays + 1 solid-state KYZ pulse output (80 mA @ 240 VAC/VDC)
Control Power 120…240 VAC @ 50/60 Hz, or 120…240 VDC, 12 VA @ 24 VDC
Web Server Built-in; configurable via webpage
Configuration Lock Switch Yes – prevents changes affecting revenue accuracy
Alarms Configurable for up to 20 events
Mounting Panel-door or DIN-rail (with adapter)
Enclosure Rating Indoor use only
Operating Temperature −20…70 °C
Storage Temperature −40…85 °C
Humidity 5…95% RH, non-condensing
Altitude 2000 m maximum
Vibration 2 G
Shock 50 G, non-operating
Dielectric Withstand UL 61010, EN 61010
Weight 1.85 kg
Dimensions (H × W × D) 132 × 185 × 178 mm
Certifications UL Listed Component, cULus, CE, UKCA, Australian RCM
Warranty 12-month standard warranty