Honeywell 8U-TAIX61 51306977-175 16-Channel Analog Input IOTA with 16-Bit Resolution

Honeywell 8U-TAIX61 51306977-175 16-Channel Analog Input IOTA with 16-Bit Resolution

 

Technical Specifications

Parameter Name Parameter Value
Product Models 8C-TAIX61 (Coated), 8U-TAIX61 (Uncoated)
Part Number 51306977-175
Manufacturer Honeywell
Product Type Analog Input IOTA Module
System Compatibility Experion PKS Series 8, PlantCruise, C300 Controllers
Input Channels 16 Single-Ended
Input Signal Type 4-20 mA (2-wire or self-powered transmitters)
Input Impedance 200 Ω
A/D Converter Resolution 16 Bits
Scan Rate 50 ms
Accuracy ±0.075% of full-scale (23.5°C ± 2°C); ±0.15% of full-scale (0 to 60°C)
Normal Mode Rejection Ratio (60 Hz) 19 dB
Common Mode Rejection Ratio 70 dB
Maximum Input Voltage (No Damage) ±30 Volts
Isolation Galvanic isolation; channel-to-backplane 2500VAC
Non-Incendive Field Power Yes, with individually protected current limiting circuits for Class 1 Div 2
Operating Temperature 0°C to +60°C
Storage Temperature -40°C to +85°C
IOTA Size 12 inches (304 mm)
Module Dimensions Approx. 29.5 x 12 x 7 cm
Weight Approx. 0.38 – 0.59 kg
Protection IP20 (cabinet installation)
Certifications CE, UL, CSA, SIL 2, Class I Div 2 / Zone 2

 

Main Features and Advantages

High-Density 16-Channel Analog Input: The Honeywell 8C-TAIX61 and 8U-TAIX61 modules provide 16 single-ended analog input channels, delivering exceptional channel density in a compact 12-inch IOTA form factor . This high-density design allows system integrators to maximize I/O points within limited cabinet space, reducing overall footprint and wiring complexity. Each channel of the Honeywell 51306977-175 is optimized for 4-20 mA current signals from 2-wire or self-powered transmitters, ensuring compatibility with a wide range of industrial sensors. The 16-bit A/D converter resolution delivers precise measurement, with hardware accuracy of ±0.075% of full-scale under nominal conditions, enabling accurate process variable acquisition for demanding control applications .

Fast Scan Rate and Real-Time Performance: With a 50 ms input scan rate, the Honeywell 8C-TAIX61 and 8U-TAIX61 modules ensure rapid, deterministic data acquisition for real-time process monitoring . This fast loop scanning capability allows control strategies to respond quickly to process changes, improving overall system responsiveness and stability. The modules incorporate extensive self-diagnostics and channel-level fault detection, including loop break, short circuit, and over-range alarms, enabling proactive maintenance and minimizing unplanned downtime .

Robust Non-Incendive Field Power and Redundancy: A standout feature of the Honeywell 51306977-175 is its integrated non-incendive field power for 4-20 mA loops, eliminating the need for external user-supplied field power . Each channel includes individually protected current limiting circuits, ensuring safe interfacing with transmitters in Class 1 Division 2 hazardous environments . The and modules support optional redundancy, enabling hot-standby configurations that provide bumpless switchover in the event of a fault, maximizing system availability and operational continuity in mission-critical processes .

Coated and Uncoated Variants for Environmental Flexibility: The variant features a conformal coating that provides enhanced protection against moisture, dust, and corrosive atmospheres, making it ideal for harsh industrial environments such as chemical plants and offshore platforms . The variant offers an uncoated, cost-effective solution for standard indoor control cabinet installations . This dual-option design ensures that the Honeywell 51306977-175 family can be optimally specified for virtually any application environment.

Scroll to Top